Ventilation unit, no ducts, expanded polypropylene (EPP) casing, aluminum cross flow heat exchangers, modulating fans by german manufacturer EBM, horizontal version for ceiling mounting, delivered with a adapter OxC2-H (1 piece) dedicated for connecting unit with extension duct OxE-H, air flow 150-1200 m³/val., air stream range 4.5 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 78.1 kg, 2 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Click on the Model for technical data, dimensions, accessories
OXeN - no ducts, expanded polypropylene (EPP) casing, aluminum cross flow heat exchangers, fans by german manufacturer EBM, vertical version for wall mounting, delivered with a wall transition OxC (1 piece)
OXeN-X2-N-1.2-V Air flow 150-1200 m³/val., air stream range 15 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 75.1 kg, 2 year WARRANTY
OXeN-X2-N-1.2-V
Air flow 150-1200 m³/val., air stream range 15 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 75.1 kg, 2 year WARRANTY
OXeN-X2-W-1.2-V With additional 10 kW (water 80/60°C, air 5°C) water heat exchanger, air flow 150-1200 m³/val., air stream range 15 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 77.5 kg, 2 year WARRANTY
OXeN-X2-W-1.2-V
With additional 10 kW (water 80/60°C, air 5°C) water heat exchanger, air flow 150-1200 m³/val., air stream range 15 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 77.5 kg, 2 year WARRANTY
OXeN-X2-E-1.2-V With additional 3-steps 3.5/5.5/8.5 kW electric heat exchanger, air flow 1200 m³/val., air stream range 15 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption (without additional heat exchanger) 420 W, protection class IP42, weight 82.5 kg, 2 year WARRANTY
OXeN-X2-E-1.2-V
With additional 3-steps 3.5/5.5/8.5 kW electric heat exchanger, air flow 1200 m³/val., air stream range 15 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption (without additional heat exchanger) 420 W, protection class IP42, weight 82.5 kg, 2 year WARRANTY
OXeN - no ducts, expanded polypropylene (EPP) casing, aluminum cross flow heat exchangers, modulating fans by german manufacturer EBM, horizontal version for ceiling mounting, delivered with a adapter OxC2-H (1 piece) dedicated for connecting unit with extension duct OxE-H
OXeN-X2-N-1.2-H Air flow 150-1200 m³/val., air stream range 4.5 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 78.1 kg, 2 year WARRANTY
OXeN-X2-N-1.2-H
Air flow 150-1200 m³/val., air stream range 4.5 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 78.1 kg, 2 year WARRANTY
OXeN-X2-W-1.2-H With additional 10 kW (water 80/60°C, air 5°C) water heat exchanger, air flow 150-1200 m³/val., air stream range 4.5 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 80.5 kg, 2 year WARRANTY
OXeN-X2-W-1.2-H
With additional 10 kW (water 80/60°C, air 5°C) water heat exchanger, air flow 150-1200 m³/val., air stream range 4.5 m, heat recovery efficiency 74.7-80.9%, acoustic pressure level 49 dB(A), maks. power consumption 420 W, protection class IP42, weight 80.5 kg, 2 year WARRANTY
Model: OXeN-X2-N-1.2-H
General data
Stepless modulating air flow
m³/h
150 - 1200
Heat recovery efficiency on dry / wet air conditions (according to directive 2009/125/EC measured with balanced mass flow, an indoor-outdoor air temperature difference of 20°C)
%
74,7 / 80,9
Air flow range (measured verticaly at 0.2 m/s speed limit)
m
4,5
Fan data
Max. acoustic pressure level at a distance of 5 m from the unit, in the 500 m³ room of medium capabillity of sound absorption
dB(A)
49
Air filters data
Class
EU4
Installation data
Power supply
V/Hz
230/50
Max. power consumption
W
420
Max. current consumption
A
1,9
IP protection class
42
Installation
Horizontally under the ceiling
Max. air contamination
g/m³
0,3
Max. operating temperature
°C
5 - 45
Other data
Heat recovery exchanger
Two stage recovery, cross flow heat exchanger
Casing
EPP - expanded polypropylene
Color
Grey (similar to RAL 9007)
Control
Touchscreen control panel T-box
Anti-freeze protection for heat recovery exchanger
Decrease of supplying air volume
Dimensions
Length
mm
1370
Width
mm
1180
Height
mm
760
Weight
kg
78,1

Dimensions

Model: OXeN-X2-N-1.2-H
OXeN heat recovery unit
Manuals 2.2 MB
Declarations of conformity 347 KB
Brochures 738 KB
Catalogue 9.6 MB
Hygienic certificate 592 KB
AutoCAD drawings 1.2 MB
BIM objects 5.1 MB
T-box controller
Manuals 22.7 MB
Declarations of conformity 643 KB
MODBUS protocol for connection to BMS 6.2 MB