Gas heater, patented Robur heat exchanger in aluminium special alloy with Ground Effect, additional condensing heat exchanger, Pre-Mix burner technology, axial fan, 20.2-56.2 kW modulating heat output, modulating air flow 3310-5350 m³/h, air throw 31 m, weight 75 kg, 2 year WARRANTY
Interested in this product? Contact us:

Arvydas Palivonas

LT, RU, EN
+370 601 74426

Sales representative for Vilnius, Ukmergė, Utena, Kaišiadorys and Varėna regions Get Offer

Andrius Lekarevičius

LT, RU, EN
+370 606 11865

Sales representative for Kaunas, Panevėžys, Šiauliai, Telšiai, Klaipėda, Tauragė, Marijampolė and Alytus districts Get Offer
Click on the Model for technical data, dimensions, accessories
G series - patented Robur heat exchanger in aluminium special alloy with Ground Effect, additional condensing heat exchanger, Pre-Mix burner technology, axial fan
G 30 15.8-29.2 kW modulating heat output, modulating air flow 2300-2700 m³/h, air throw 18 m, weight 55 kg, 2 year WARRANTY
G 30
15.8-29.2 kW modulating heat output, modulating air flow 2300-2700 m³/h, air throw 18 m, weight 55 kg, 2 year WARRANTY
G 45 15.6-43.3 kW modulating heat output, modulating air flow 2340-4000 m³/h, air throw 25 m, weight 65 kg, 2 year WARRANTY
G 45
15.6-43.3 kW modulating heat output, modulating air flow 2340-4000 m³/h, air throw 25 m, weight 65 kg, 2 year WARRANTY
G 60 20.2-56.2 kW modulating heat output, modulating air flow 3310-5350 m³/h, air throw 31 m, weight 75 kg, 2 year WARRANTY
G 60
20.2-56.2 kW modulating heat output, modulating air flow 3310-5350 m³/h, air throw 31 m, weight 75 kg, 2 year WARRANTY
G 100 33.5-90.2 kW modulating heat output, modulating air flow 5200-8250 m³/h, air throw 40 m, weight 120 kg, 2 year WARRANTY
G 100
33.5-90.2 kW modulating heat output, modulating air flow 5200-8250 m³/h, air throw 40 m, weight 120 kg, 2 year WARRANTY
  G 30 G 45 G 60 G 100
Heat input max. kW 30 45 58 93
min. kW 15 15 19.3 31.7
Nominal heat output max. kW 29.2 43.3 56.2 90.2
min. kW 12.6 15.6 20.2 33.5
Efficiency max. output % 97.3 96.3 97.0 97.0
min. output % 105.3 104.3 104.6 105.7
Gas consumption1 natural gas m3/h 3.17 4.76 6.14 9.84
LPG kg/h 2.33 3.50 4.53 7.26
Airflow rate2 max. m3/h 2700 4000 5350 8250
min. m3/h 2300 2340 3310 5200
Temperature rise at maximum speed °C 31.1 31.8 30.8 32.1
at minimum speed3 °C 16.3 19.6 17.9 18.9
Gas connection ”M 3/4"
Air inlet pipe diameter mm 80
Exhaust flue pipe diameter mm 80
Electrical supply   230 V 1N - 50 Hz
Installed wattage W 350 450 750 900
Air throw at maximum speed in free field4 m 10 25 31 40
Recommended height of installation m 2.5 2.5-3 3-3.5 3-4
Operating temperature range5 °C 0-35
Sound pressure level at the max speed at 6 meters distance in open field dB(A) 47 48 50 54
in typical installation dB(A) 59 60 61.5 65.5
Sound pressure level at the min speed at 6 meters distance in open field dB(A) 42 43 45 49
in typical installation dB(A) 54 55 56 60.5
Dimensions width mm 656 706 796 1296
depth mm 735 735 760 740
height mm 800
Weight kg 55 66 76 122
  1. At 15 °C - 1013 mbar.
  2. At 20 °C - 1013 mbar.
  3. Temperature rise of the air which permits to maintain the outlet air flow at a higher temperature than the one of the human body for a better comfort.
  4. Throw for guidance only. Throw depends on height of building, mounting height to heater, room temperature and louvre setting.
  5. Indoor temperature of the installation location. The unit’s internal components have been tested from 0°C to 60°C.

Technical data

Model: G 60
General data
Nominal heat output (min - max)
kW
19.3 - 58
Delivered